Siting - Smoke Alarms
Mount centrally on the ceiling
Keep at least 300mm (12") from walls
Keep at least 300mm (12") from light fittings
There must be an alarm within 3m (10ft) of all bedroom doors
On peaked ceilings, mount 900mm (36") horizontally from the peak
Keep at least twice the depth away from any small obstructions, such as beams
Any obstruction greater than 10% of the room height should be treated as a wall
Extra alarms may be needed
Siting - Control Switches & Call Points
Mount 1.2m (4ft) from floor level
Control Switches should be mounted somewhere that's easy to access
Call points should be mounted by final exits from the building
Siting - Carbon Monoxide (CO) Alarms
Ceiling mounted
Between 1m and 3m horizontally from the appliance
Keep at least 300mm (12") from walls
Keep at least 300mm (12") from light fittings
Wall mounted
Fit at breathing height
Siting - Alarms for Hearing Impaired
Wall mounted
Strobe must be visible
Put vibrating pad under pillow