Alarm Siting

Overview of Alarm Siting

Siting alarms correctly throughout a property is vital to ensure they provide life saving detection and respond as quickly as possible in the event of a fire or carbon monoxide leak. Every property is different, but here are some basic rules to follow when considering siting:

Smoke and Heat Alarms

  • Alarms should be sited on the ceiling, as centrally as possible within the room/area they are installed
  • Site 300mm from walls and light fittings – this is to ensure that they are outside of any ‘dead air’ spaces that occur in corners and spaces where the airflow may be blocked

Siting - Standard Space

  • There should be an alarm within 3m of every bedroom door to ensure audibility
  • Alarms should be positioned between high risk rooms and bedrooms
  • Alarms should not sited within bathrooms or too close to a bathroom door as steam/moisture can affect them
  • There should be an alarm within 3m of each escape door

Single Storey Alarm Siting

Other factors to consider:

  • Where stairways are present site alarms on the flat ceilings at the top and bottom of the stairs – do not site on the sloped ceiling directly above the stairs
  • Peaked and sloped ceilings – for smoke alarms site a maximum of 600mm vertically down from the apex, for heat alarms a maximum of 150mm vertically down from the apex

Sloped Roof Siting

Peaked Ceiling Siting

  • Beams (where the depth of the beam is less than 10% of the room height) – site the alarm twice the depth of the beam or 500mm, whichever is less

Siting - Beams - Below 10%

  • Beams (where the depth of the beam is more than 10% of the room height) – treat the beam as a wall and fit alarms on both sides of the beam, or if the beam is less than 600mm deep site an alarm on the underside of the beam

Siting - Beams - Over 10%

 

Carbon Monoxide Alarms

When installing Carbon Monoxide alarms it’s important to note that there are different siting requirements depending upon if the alarm is being installed in the room with the fuel-burning appliance or not.

In a room with the fuel burning appliance:

  • Alarms should be sited on the ceiling
  • Should be fitted between 1m–3m from all potential sources of Carbon Monoxide
  • Sited 300m from walls and light fittings – this is to ensure that they are outside of any ‘dead air’ spaces that occur in corners and spaces where the airflow may be blocked
  • If the fuel burning appliance is in a confined space, for example a boiler room then the alarm should be sited on the ceiling just outside the room

Carbon Monoxide Alarm Siting

In a room without a fuel burning appliance:

  • Alarms should be sited at breathing height
  • If installed within a bedroom, this could be at the height of the bedhead

 

For more information please refer to the British Standard BS 5839-6:2013 for smoke/heat alarms, British Standard BS EN 50292:2013 for carbon monoxide alarms or the relevant Building Regulations. You can also contact our Technical team for advice at technical@aico.co.uk.